TVR Instruments Measuring Power Protection LVD Distribution & Panel Building

 

 

 

Tel: 01206 575755
sales@tvri.co.uk

Amps Membership  FSB Membership facebook TVR Instruments Ltd linkedin TVR Instruments Ltd twitter TVR Instruments Ltd

Digital Earth Leakage Relays for type b applications X --- DB3 Series

The X...DB3 series earth leakage relays type B are designed to measure the DC, AC and high frequency leakage current. Having an LCD display it allows a continuous monitoring of the insulation state. This will allow for a program of preventive maintenance to avoid unexpected power outages.

The units are available in a DIN Rail mounting 36 mm version, and either a 48 or 72 mm panel mounting housing. The LCD backlight changes colour to indicate measure, alarm and trip status for quick and clear indication of network health. The three backlight colours are green, amber and red.

The TBD sensors for monitoring the combined AC and DC lines are available with a 28, 60 or 90 mm cable passing aperture. Care must be taken in the installation of the sensors to ensure cables pass in the centre.

Digital Earth Leakage Relays X --- DB3 Series

Main Features
earth Leakage Continuous digital indication of the leakage current: total earth Leakage Storing of the intervention current values
  RMS, AC fundamental, AC high frequency earth Leakage RS485 Modbus RTU, measurements, event archive, scope
earth Leakage Double threshold: total RMS and DC component earth Leakage Selectable 3rd harmonic filter
earth Leakage AC measurements up to 10kHz earth Leakage Selectable ant fibrillation filter with fire protection 300 mA
earth Leakage Internal clock and storage of the last 10 events
  Datasheet Digital Earth Leakage Relays X --- DL3 Range  

 