TVR Instruments Measuring Power Protection LVD Distribution & Panel Building

 

 

 

Tel: 01206 575755

twitter TVR Instruments Ltd  FSB Membership TVR Shop  

GENSET CONTROLLER - Automatic Transfer & Load Share Unit With Mains


trans-mains genset controllers

 

TRANS-MAINS

Load sharing with genset (up to 32 gensets) Busbar voltages and frequency measurements Bus failure detection Peak lopping (mains or genset) Power export to mains Mains de-coupling protection with R.O.C.O.F and vector shift methods Volts, frequency and phase matching Synchroscope display Logic Controller functionality for PLC.

Data Sheet Manual

Specifications
Communication interface USB programming and communication port, CanOpen, Ethernet, RS485.
Inputs 13x Configurable digital
Outputs Configurable 9x Transistors, GBR outputs
Current Measurement 3 phases CT inputs for Load Current, 1x CT input for Earth Current
Voltage Measurement 3 phases for Alternator
Power Factor Measurement For 3 phases
Case
Dimensions 276mm x 189mm x 45mm
Panel Cut-Out 223mm x 162mm
Protection IP65 at front side
Weight Approximately 0,82Kg
Ratings
DC Battery Supply range 8 to 32Vdc, max.operating current is 860mA
CT Secondary 5A
Sender Measurement

0 to 1300 ohm, accuracy: 1%FS, resolution: 1 ohm

Cabin.Temp.Measuremet

-50 to +100 ºC, accuracy: 1 % FS, resolution: 1 ºC.
Operating / Storage Temp. -20°C to +70°C / -30°C to +80°C

 


  TVR Instruments Limited, 143 Butt Road, Colchester CO3 3DP, Essex, United Kingdom - Tel: +44 (0)1206 575755 - Email
Company Registration No. 7850289 © TVR Instruments Limited 2011 - Subscribe to TVR Newsletters/Product Updates