TVR Instruments Measuring Power Protection LVD Distribution & Panel Building

 

 

 

Tel: 01206 575755


LinkedIn  FSB Membership TVR Shop UK GEN-SET & CHP Association

UFR1002IP Voltage and Frequency Relay G99 & G99NI Compliant


The grid decoupling relay UFR1002IP is the latest addition to the G99 compliant relays alongside the UFR1001E. It monitors voltage and frequency in three-phase and AC grids with remote monitoring via an ethernet connection. Using the VG1200, there is the ability to be used on 1200V AC systems.

UFR1002IP Voltage and Frequency Relay

The UFR1002IP is compliant with G99 & G99NI and is approved on the ENA Direct Registry.

With a coloured LCD display and joystick for menu navigation, the UFR1002IP is very easy to use. The measured values and settings are clearly displayed. The device can be programmed, updates installed and the alarm memory read out via the integrated IP interface. The real-time clock (with power reserve) simplifies the traceability of the alarms. Up to 1200 V can be monitored in conjunction with the VG1200 coupling device. The device has a two-channel, single-fault-safe design and thus meets the requirements of VDE-AR-N 4105:2018-11. The function of the connected switch is monitored. If monitoring is activated, the device does not switch on again if a switch-off error is detected.

Limit values for different applications are preset. Where permitted, they can easily be changed. If the nominal voltage is changed, the device automatically adjusts the limit values. With the standby input, a remote shutdown can be implemented, e.g. with a ripple control receiver.

Monitoring of:

  • Under/over voltage 15-520V (with ZIEHL VG1200 coupling device up to 1,200 V)
  • Under/over frequency 45-65 Hz
  • Voltage quality (10-minute average)
  • Vector shift 2-65°
  • ROCOF, rate of change of frequency df/dt 0.100...5.000 Hz/s
  • Zero voltage U0 (ANSI 59v0)
  • passive anti islanding protection

Features:

  • Compliant with G99 & G99NI and is approved on the ENA Direct registry.
  • single-fault-proof, with monitoring of connected switch (can be switched off when using the integrated switch of PV and battery converters
  • Programmable restart attempts in the event of a switch-on error in the connected switch
  • Relay K3 with programmable functions, including life contact, delayed switch-on signal for switches or error messages
  • Response time adjustable 0.05 … 300,0 s
  • Switch-back time adjustable 0 … 6,000 s
  • Preset according to G99 for the UK market
  • Preset according to VDE-AR-N 4105-2018-11 (Pr 1.02, Pr 1.08 + 1.09) and VDE-AR-N 4105-2011-08 (Pr 1.01)
  • Preset according to VDE-AR-N 4110-2018-11 (Pr 1.11-1.14) and bdew guideline (Pr 1.03-1.06)
  • automatic adjustment of the switching points when the nominal voltage is changed
  • Alarm counter for 100 alarms (with trigger value, cause and date/time, time of restart)
  • 3 programmable digital inputs
  • Standby counter and timer with standby on/off date/time
  • Test and simulation function with measurement of switch-off times
  • Sealing option and code protection for settings
  • Interface ethernet TCP/IP, values available via modbus TCP
  • Simple commissioning and programming thanks to preset basic programs and transmission via IP interface
  • Supply voltage AC/DC 24-270 V
  • Housing for DIN-rail-mount, 105 mm wide, mounting height 66 mm
  • Accessory: Installation frame ER6 for panel mount
Datasheet
Operating Manual
Operating Manual - ModBus
Quick Guide
Certificate of Compliance Great Britain: UFR1002IP
Certificate of Compliance Great Britain: FR 1002IP optional with VG1200
Certificate of Compliance Great Britain: UFR 1002IP including VG1200
UFR1002IP - Visit TVR Instruments Online Shop

 

 

 


  TVR Instruments Limited, 143 Butt Road, Colchester CO3 3DP, Essex, United Kingdom - Tel: +44 (0)1206 575755 - Email /
Company Registration No. 7850289 © TVR Instruments Limited 2011 - Subscribe to TVR Newsletters/Product Updates
/ Terms & Conditions
return to top of page